The Megger MIT420/2 is a CAT IV 600 V insulation and continuity tester with stabilised test voltages from 50 V to 1000 V, a variable 10 V to 1000 V range, insulation measurement up to 200 GΩ, PI/DAR and timed tests, 600 V TRMS voltage, capacitance and storage of over 1000 results.
The Megger MIT420/2 belongs to the MIT400/2 (mk2) series of CAT IV insulation and continuity testers. It is designed for electrical and industrial testing and for an exceptionally wide range of applications, including electrical installations, cable testing, motor testing, automotive, ESD, panel building, avionics and maintenance.
Insulation tests run at 50 V, 100 V, 250 V, 500 V and 1000 V, or at any voltage from 10 V to 1000 V in 1 V steps using the variable range. The test voltage is feedback-controlled and held within -0% +2% throughout the test range, compared with the industry standard of +20%, giving an accurate test voltage without the risk of over-voltage damage to circuits or components. Insulation resistance is measured up to 200 GΩ at 1000 V, with Polarization Index (PI), Dielectric Absorption Ratio (DAR) and timed tests.
A single auto-ranging continuity function covers 0.01 Ω to 1.0 MΩ at 200 mA or 20 mA, and True RMS voltage is measured up to 600 V AC/DC with automatic frequency display. The MIT420/2 also measures capacitance and stores more than 1000 test results. The over-moulded case is sealed to IP54, including the battery and fuse compartment, and the instrument is rated CAT IV 600 V.
| Manufacturer | Megger |
|---|---|
| Model | MIT420/2 (order code 1004-739) |
| Insulation test voltages | 50 V, 100 V, 250 V, 500 V, 1000 V |
| Variable test voltage | 10 V to 1000 V in 1 V steps |
| Insulation range | 50 V: 10 GΩ · 100 V: 20 GΩ · 250 V: 50 GΩ · 500 V: 100 GΩ · 1000 V: 200 GΩ |
| Insulation accuracy (at +20 °C) | 50 V: ± 2% ± 2 digits ± 4.0% per GΩ · 100 V: ± 2% ± 2 digits ± 2.0% per GΩ · 250 V: ± 2% ± 2 digits ± 0.8% per GΩ · 500 V: ± 2% ± 2 digits ± 0.4% per GΩ · 1000 V: ± 2% ± 2 digits ± 0.2% per GΩ |
| Insulation service error (BS EN 61557-2 (2007), 100 kΩ - 900 kΩ) | 50 V: ± 10.5% · 100 V, 250 V, 500 V: ± 10.3% · 1000 V: ± 11.5% |
| Insulation resolution | 0.1 kΩ |
| Analogue display range | 1 GΩ full scale |
| Short circuit/charge current | 2 mA +0% -50% to EN 61557-2 (2007) |
| Open circuit voltage (insulation) | -0% +2% ± 2 V |
| Insulation test current | 1 mA at min. pass value of insulation, 2 mA max. |
| Leakage current accuracy | 10% ± 3 digits |
| Test voltage display accuracy | 3% ± 3 digits ± 0.5% of rated voltage |
| PI / DAR | PI: 10 min / 1 min ratio · DAR: 60 s / 15 s or 60 s / 30 s ratio |
| Timer control | 60 second countdown timer |
| Live circuit test inhibit | 25 V, 30 V, 50 V, 75 V or 100 V (default 50 V) |
| Continuity range | 0.01 Ω to 1000 kΩ |
| Continuity accuracy | ± 3% ± 2 digits (0 to 100 Ω) · ± 5% ± 2 digits (100 to 500 kΩ) · 500 kΩ to 1 MΩ unspecified · Service error BS EN 61557-4 (2007), 0.1 Ω - 2 Ω: ± 6.8% |
| Continuity open circuit voltage | 5 V ± 1 V |
| Continuity test current | 200 mA (–0 mA +20 mA) (0.01 Ω to 4 Ω) or 20 mA |
| Continuity buzzer limit | 1 Ω to 200 Ω in 12 steps |
| Polarity | Single polarity (default) / dual polarity (configurable in setup) |
| Voltage range | AC: 10 mV to 600 V TRMS sinusoidal (15 Hz to 400 Hz) · DC: 0 to 600 V |
| Voltage resolution | From 0.1 mV |
| Voltage accuracy | AC: ± 2% ± 1 digit · DC: ± 2% ± 2 digits · Service error BS EN 61557-1 (2007), 0 V – 300 V AC/DC: ± 5.1% |
| Non-sinusoidal waveforms | ± 3% ± 2 digits (>100 mV to 600 V TRMS) · ± 8% ± 2 digits (10 mV to 100 mV TRMS) |
| Input impedance | 0.25 MΩ |
| Frequency measurement | 15 Hz - 400 Hz, ± 0.5% ± 1 digit (100 Hz to 400 Hz unspecified) |
| Capacitance measurement | 1 nF to 10 μF, ± 5.0% ± 2 digits (0.1 nF – 1 nF unspecified) |
| Result storage | >1000 test results |
| Display | Analogue arc and dual digital readout |
| Power supply | 6 x 1.5 V cells type IEC LR6 (AA, MN1500, HP7, AM3 R6HP) alkaline, or 6 x 1.2 V NiMH rechargeable cells |
| Battery life | 3000 insulation tests with duty cycle of 5 s ON / 55 s OFF @ 1000 V into 1 MΩ |
| Fuse | 1 x 500 mA (FF) 1000 V 32 x 6 mm ceramic, HBC 30 kA minimum |
| Safety | IEC 61010 and EN 61557; EN 61010-1 (1995) to 600 V phase to earth, Category IV; CAT IV 600 V / CAT III 1000 V |
| EMC | IEC 61326 including amendment No.1 |
| Temperature coefficient | <0.1% per °C up to 1 GΩ · <0.1% per °C per GΩ above 1 GΩ |
| Operating temperature and humidity | -10 to +55 °C · 90% RH at 40 °C max. |
| Storage temperature | -25 to +70 °C |
| Calibration temperature | +20 °C |
| Maximum altitude | 2000 m |
| IP rating | IP54 |
| Dimensions | 228 × 108 × 63 mm (9.00 × 4.25 × 2.32 in) |
| Weight (instrument and case) | 1.75 kg (3.86 lb) |